Image Alt

All Product

  /    /  Phoenix Contact  /  PHOENIX CONTACT FLS PB M12 DI 16 M12
0%

    PHOENIX CONTACT FLS PB M12 DI 16 M12

    230.00

    1 in stock

    1 in stock

    Quantity
    SKU: 2736220 Category: Tags: ,

    Product description

    PROFIBUS DP
    Connection method 2x M12 connectors, B-coded
    Designation connection point Copper cable
    Number of positions 5
    Transmission speed 9.6 kbps … 12 Mbps (Automatic baud rate detection)
    Transmission physics PROFIBUS-DP-compliant copper cable
    Address area assignment 1 … 99, can be set

    System limits
    Number of local bus devices that can be connected 0
    Number of devices with parameter channel 0
    Module
    ID code (hex) 06FB
    Input address area 16 bit
    Output address area 0 bit
    Register length 8 bit

    Digital:
    Input name Digital inputs
    Description of the input IEC 61131-2 type 1
    Number of inputs 16
    Connection method M12 connector, double occupancy
    Connection technology 2-, 3-, 4-conductor
    Input voltage 24 V DC
    Input voltage range “0” signal -30 V DC … 5 V DC
    Input voltage range “1” signal 13 V DC … 30 V DC
    Nominal input voltage UIN 24 V DC
    Total sensor current max. 1200 mA
    Filter time 1 ms
    Protective circuit Reverse polarity protection

    Product type I/O component
    Product family Fieldline
    Type Block design
    No. of channels 16

    Maximum power dissipation for nominal condition 31.2 W
    Potentials
    Voltage supply UL 24 V DC
    Power supply at UL max. 4 A
    Current consumption from UL typ. 35 mA
    max. 100 mA
    Voltage supply US 24 V DC
    Power supply at US max. 4 A
    Current consumption from US typ. 8 mA (plus sensor current)
    max. 1.2 A
    Supply: Module electronics
    Connection method M12 connector (A-coded)
    Designation UL
    Supply voltage 24 V DC
    Supply voltage range 18 V DC … 30 V DC (including ripple)
    Electrical isolation/isolation of the voltage ranges
    Test voltage: 24 V supply (bus logics) / FE 500 V AC, 50 Hz, 1 min.
    Test voltage: 24 V supply (bus logics) / Digital inputs (sensor supply) 500 V AC, 50 Hz, 1 min.
    Test voltage: Bus connection / FE 500 V AC, 50 Hz, 1 min.
    Test voltage: Bus connection / Digital inputs (sensor supply) 500 V AC, 50 Hz, 1 min.
    Test voltage: FE / Digital inputs (sensor supply) 500 V AC, 50 Hz, 1 min.

    Connection method M12 connector

    Ambient conditions
    Ambient temperature (operation) -25 °C … 60 °C
    Degree of protection IP65/IP67
    Air pressure (operation) 80 kPa … 106 kPa (up to 2000 m above sea level)
    Air pressure (storage/transport) 70 kPa … 106 kPa (up to 3000 m above sea level)
    Ambient temperature (storage/transport) -25 °C … 85 °C
    Permissible humidity (storage/transport) 95 %

    Protection class III (IEC 61140, EN 61140, VDE 0140-1)

    Mounting type Wall mounting

    Additional information

    Weight 0.35 kg
    Dimensions 1.61 × 6 × 44.5 cm